ET48300005 5U 18kW 48V 300A DC Telecom Power System with Six 3kW Rectifiers and Front Service Distribution

基本プロパティ
原産地: 中国
ブランド名: ESTEL
認証: CE UL FCC
取引物件
最低注文数量: 1セット
価格: USD300-USD1000
支払い条件: T/T、ウェスタンユニオン
補給能力: 5000
製品概要
ET48300005 5U 18kW 48V 300A DC Telecom Power System with Six 3kW Rectifiers and Front Service Distribution The ET48300-005 is a 5U rack-mounted DC telecom power system developed for communication sites that need dependable -48V power, organized load distribution and battery backup in a compact ...

プロダクト細部

ハイライト:

48V telecom power system with 300A

,

5U 18kW DC power system

,

telecom power system with rectifiers

Solar Array: 580W ソーラーパネル 24 枚
Input Capacity: 1×63a/2p
Thd: 抵抗負荷で<1,5%
Dc Load Breakers: 30 職種
Efficiency: 90%以上
Certifications: ISO9001のセリウム、RoHS
Package: カートン
Poweroutput: 10kW~100kW
Ac Frequency: 50Hz,60Hz または最後に同期された
Load Protection: LLVD、BLVD
Protectionfeatures: 過電圧、過電流、短絡、過熱
Dc Current Max: 53.5 VDC/43 - 58 VDC
Dc Output Breakers: 4
Frequency: 45 〜 66 Hz
Industrial Ac Input: 各直線器の単相
製品説明

 

ET48300005 5U 18kW 48V 300A DC Telecom Power System with Six 3kW Rectifiers and Front Service Distribution

 
 
The ET48300-005 is a 5U rack-mounted DC telecom power system developed for communication sites that need dependable -48V power, organized load distribution and battery backup in a compact cabinet space. It is positioned as an 18kW / 300A class solution, using six 3kW rectifier modules to provide stable DC output for transmission equipment, access devices, switches and base-station loads.
 
This model is suitable for sites using 220VAC single-phase input, making it easier to deploy in equipment rooms or access network cabinets where three-phase power is not available. The system integrates AC input protection, AC surge protection, rectification, battery breakers, LLVD/BLVD load outputs, DC SPD, LCD monitoring and communication terminals into one front-service platform. The front panel layout allows technicians to check breaker status, controller alarms and wiring terminals without removing the system from the rack.

Product Features 18kW 48V 300A DC Telecom Power System

 

18kW modular capacity: Six 3kW rectifiers support flexible configuration and online maintenance.

 

300A DC output class: Suitable for medium to high-load telecom power distribution.

 

Single-phase AC input: Designed for 220VAC sites with 1 × 100A/2P input protection.

 

Clear load separation: LLVD and BLVD branches help divide priority and non-priority equipment.

 

Battery protection: Two 125A battery breakers support backup battery connection and isolation.

 

Surge protection: Integrated AC SPD and DC SPD improve system resistance to transient overvoltage.

 

Remote monitoring support: LCD controller with RS485, SNMP, dry contacts, AI/DI signal inputs.

 

Front maintenance design: Rectifier and controller are hot-pluggable for faster field replacement.

 

Application Scenarios 18kW 48V 300A DC Telecom Power System

 
The ET48300-005 is suitable for wireless base stations, transmission networks, fiber access sites, enterprise communication rooms, microwave stations, telecom cabinets and backup DC power systems requiring stable -48V distribution with battery management.
 

Technical Parameters 18kW 48V 300A DC Telecom Power System

 

Model: ET48300-005

 

Type: 3–18kW 5U Subrack

 

Maximum Current: 300A

 

Dimensions: 482.0(W) × 350.6(D) × 5U(H)

 

Weight: ≤22kg without rectifiers

 

Installation: 19-inch rack or cabinet

 

Cabling: Top inlet and top outlet

 

Protection Level: IP20

 

AC Input: 220VAC single phase

 

Input Capacity: 1 × 100A/2P

 

Frequency: 45–65Hz, rated 50/60Hz

 

AC SPD: 20kA/40kA, 8/20μs

 

DC Output: -43V to -58VDC, rated -53.5VDC

 

Maximum Capacity: 18kW, 6 × 3kW

 

Battery Breakers: 2 × 125A/1P

 

LLVD: 2 × 32A/1P + 2 × 40A/1P + 3 × 63A/1P

 

BLVD: 2 × 6A/1P + 2 × 10A/1P + 2 × 16A/1P

 

DC SPD: 10kA/20kA, 8/20μs

 

Rectifier Efficiency: >96%

 

Power Factor: ≥0.99

 

Operating Temperature: -40°C to +75°C

 

Humidity: 5%–95%, non-condensing

 

Altitude: 0–4000m

 

ET48300005 5U 18kW 48V 300A DC Telecom Power System with Six 3kW Rectifiers and Front Service Distribution 0

ET48300005 5U 18kW 48V 300A DC Telecom Power System with Six 3kW Rectifiers and Front Service Distribution 1

ET48300005 5U 18kW 48V 300A DC Telecom Power System with Six 3kW Rectifiers and Front Service Distribution 2

ET48300005 5U 18kW 48V 300A DC Telecom Power System with Six 3kW Rectifiers and Front Service Distribution 3

関連製品
  • 28U インテグレテッドアウトドアパワーキャビネット 矯正システムUPS バッテリーエネルギー貯蔵庫

    28U インテグレートアウトドア電源キャビネット 矯正システムUPS バッテリーエネルギー貯蔵 1簡単な紹介: 屋外電信キャビネットは,通常,電信機器の保護と機能を確保するためのさまざまな機能が備わっています.屋外電信キャビネットの一般的な特徴には以下が含まれます. 天気 に 耐える デザイン: 屋外 の キャビネット は,雨,雪,極端 な 温度,塵 の よう な 厳しい 天気 に 耐える よう に 設計 さ れ て い ます.通常は,ステンレス鋼やアルミニウムなどの耐久性のある材料ででき,水や塵に対する保護レベルを示すIP (イングレス・プロテクション) 評価があります.. 熱管理:屋外キ...
  • 屋外力キャビネット、水センサー/ドア センサーが付いている屋外の電気通信のキャビネット

    屋外力キャビネット、水センサー/ドア センサーが付いている屋外の電気通信のキャビネット 1. 記述 キャビネットは1つのコンパートメント キャビネットである。キャビネットの冷却の使用エアコンおよび熱交換器は安定した温度較差で、装置を保障するために、装置大いにより長く作るためにおよびより安定した性能の耐用年数を正常に作動する。 2. 適用 DDTE069屋外の電気通信装置のキャビネットは4Gシステム、コミュニケーション/ネットワークの統合サービス、アクセス/伝達切換えのような無線コミュニケーション基地局で主に、場所、緊急コミュニケーション/伝達、等使用される。 3. 速い細部 原産地:シンセン...
  • 温度調整の発電機のソケットとの屋外の電気通信のキャビネットIP55の進入保護

    温度調整発電機のソケットが付いている屋外力キャビネット/屋外の電気通信のキャビネット 1. 指定 (1)技術的な変数 進入保護:IP55 等級B電光証拠:体言:最高60KA。:100KA 温度:働く温度:-40°C | +55°C 保管温度:-50°C | + 70°C 輸送の温度:-50°C | +70°C 相対湿度:5% | 100% 空気圧:62kpa | 0m | 5000mの高度類似した)に101kpa ( 太陽放射:1120 × (1±5%)のW/m2 (2)付属品はリストする いいえ。 項目 量 単位 Specs 1 屋外力キャビネット 1 置きなさい (1)外のり寸法:W×D...
  • エマーソン整流器/電池屋外力キャビネット サンドイッチ構造のパネルIP55

    サンドイッチ構造のパネルのエマーソン整流器および電池が付いている屋外の電源のキャビネット 1つの製品の説明 1.1出現 キャビネットが取付けられていた後図1および図2に示すように 図1 図2 1.2キャビネット構成 このプロジェクトの屋外の統合されたキャビネット構成は次の通りある: キャビネットのタイプ 構成 量 指定 主要なキャビネット 19インチの標準的な棚 1 31U 電池ケース 1 1つの層W×D×H 800×800×350 mm 照明 1 48V DC、LEDライト 空気調節 1 AC 220V入力、冷却容量1500W 空気調節 1 DC 48Vの入力、冷却容量300W 銅棒を基づか...

問い合わせを送る